| Generating Set Functional Test Report | ||||||||
| In accordance with ISO 8528 - 6 2005 | ||||||||
| PLANT NUMBER: | E11061/E | CE: | NO | |||||
| RATED OUTPUT | KVA | 150 | RATING CLASSIFICATION | PRP | ||||
| KW | 120 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 216 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50.0 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | ELECTRONIC | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | YD51441 | |||||
| ENGINE MODEL | 1006 TAG2 | SERIAL NUMBER | U932172V | |||||
| ALTERNATOR MAKE | MECC-ALTE | |||||||
| ALTERNATOR MODEL | ECP34-2L/4 | SERIAL NUMBER | 0001580140 | |||||
| CONTROL PANEL(S) | DSE 7220 | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 50.0 | 400 | 86 | 60 | 6.2 | ||
| standby / prime+10% | 110% | 50.0 | 400 | 190 | 132 | 80 | 4.5 | |
| GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) | IP | |||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 99.5 | DENSITY | 99.5 | |||||
| TEMPERATURE (Deg c) | 19 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 75 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | grustill | DATE | 22.04.2016 03.09.2012 | |||||