Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E9810 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ELECTRONIC COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER YD51440
ENGINE MODEL 1006TAG SERIAL NUMBER U911813T
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI274E SERIAL NUMBER 0269528/026
CONTROL PANEL(S) 7120 SERIAL NUMBER(S) 3035353
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 380 107 70 5
standby / prime+10% 110% 50 380 180 119 82 3.9
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.9 DENSITY 100.9
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 59 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 05.08.2010