Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11393/B CE: NO
RATED OUTPUT KVA 159 RATING CLASSIFICATION PRP
KW 127
PHASE 3
VOLTS 220 PERFORMANCE CLASS G1
AMPS 417 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE ELETRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER YD51440
ENGINE MODEL 1006TAG SERIAL NUMBER U950703X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP34-2L/4 SERIAL NUMBER 001693609
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60 220 166 63 - - 5.06
standby / prime+10% 110% 60 220 366 139 82 - 3.32
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.2 DENSITY 102.2
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 77 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 01.08.2013