Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10758/C CE: NO
RATED OUTPUT KVA 125 RATING CLASSIFICATION PRP
KW 100
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 181 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER YD51440
ENGINE MODEL 1006TAG SERIAL NUMBER U929464V
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP 34-1L/4 SERIAL NUMBER A1061991
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 94 65 - - 5.0
standby / prime+10% 110% 50.0 400 159 110 76 - 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.4 DENSITY 101.4
TEMPERATURE (Deg c) 1 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 100 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 19.12.2011