Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
PLANT NUMBER: | E11317/F | CE: | NO | |||||
RATED OUTPUT | KVA | 105 | RATING CLASSIFICATION | PRP | ||||
KW | 84 | |||||||
PHASE | 3 | |||||||
VOLTS | 415/240 | PERFORMANCE CLASS | G1 | |||||
AMPS | 146 | (AS DEFINED BY ISO 8528-1) | ||||||
HZ | 50.0 | |||||||
RPM | 1500 | |||||||
GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
ENGINE MAKE | PERKINS | BUILD NUMBER | YB51439 | |||||
ENGINE MODEL | 1006TG2A | SERIAL NUMBER | U945545W | |||||
ALTERNATOR MAKE | MECC-ALTE | |||||||
ALTERNATOR MODEL | ECP34-1L/4 | SERIAL NUMBER | 1672495 | |||||
CONTROL PANEL(S) | 7110 | SERIAL NUMBER(S) | ||||||
SWITCHGEAR | SERIAL NUMBER(S) | |||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | 55% | 50.8 | 416 | 64 | 46 | 5.5 | ||
standby / prime+10% | 110% | 50.0 | 415 | 129 | 92 | 84 | 4.2 | |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) | 98.9 101.8 | DENSITY | 101.8 | |||||
TEMPERATURE (Deg c) | 17 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
HUMIDITY (%) | 78 | LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE | CONTROL PANEL(S) | |||||||
TESTED BY | ijohnson | DATE | 22.04.2016 26.06.2013 |