Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10806 CE: NO
RATED OUTPUT KVA 103 RATING CLASSIFICATION PRP
KW 82.4
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 157 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER YB51439
ENGINE MODEL 1006TG2A SERIAL NUMBER U935493V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI274D SERIAL NUMBER 0280724/001
CONTROL PANEL(S) COMAP AMF25 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 75% 50.0 380 94.2 61.8 5.2
standby / prime+10% 110% 50.0 380 138.1 90.6 80 4.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.1 DENSITY 101.1
TEMPERATURE (Deg c) 5 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 20.01.2012