Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E11071/D | CE: | NO | |||||
| RATED OUTPUT | KVA | 125 | RATING CLASSIFICATION | PRP | ||||
| KW | 100 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 380/220 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 190 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 60 | |||||||
| RPM | 1800 | |||||||
| GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | YB37574 | |||||
| ENGINE MODEL | 1006TG2A | SERIAL NUMBER | U943251W | |||||
| ALTERNATOR MAKE | MECC-ALTE | |||||||
| ALTERNATOR MODEL | ECP34-1L4 | SERIAL NUMBER | 0001570471 | |||||
| CONTROL PANEL(S) | 7120 | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | 75% | 61.8 | 380 | 114 | 75 | 5.8 | ||
| standby / prime+10% | 110% | 60.0 | 380 | 167 | 110 | 82 | 4.6 | |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 101.2 | DENSITY | 101.2 | |||||
| TEMPERATURE (Deg c) | 16 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 89 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | ijohnson | DATE | 22.04.2016 30.08.2012 | |||||