Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11384 CE: NO
RATED OUTPUT KVA 300 RATING CLASSIFICATION PRP
KW 240
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 434 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER XGFF7149
ENGINE MODEL 1606A-E93TAG5 SERIAL NUMBER N11135W
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 38-3LN/4 SERIAL NUMBER 0001691113
CONTROL PANEL(S) DSE 8610 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 173 120 22 - 4.3
standby / prime+10% 110% 50.0 400 381 264 87 - 3.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 64 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 02.04.2014