Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11380/C CE: NO
RATED OUTPUT KVA 300 RATING CLASSIFICATION PRP
KW 240
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 433 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER XGFF7149
ENGINE MODEL 1606A-E93TAG5 SERIAL NUMBER N11693W
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO38-2LN SERIAL NUMBER 0001685277
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 138 96 - - 4.34
standby / prime+10% 110% 50 400 381 264 86 - 2.33
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.3 DENSITY 102.3
TEMPERATURE (Deg c) 24 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 64 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 16.07.2013