Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11603/K CE: NO
RATED OUTPUT KVA 250 RATING CLASSIFICATION PRP
KW 200
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 361 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGHF7204
ENGINE MODEL 1306-E87TAG6 SERIAL NUMBER N11703X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO38-1LN SERIAL NUMBER 1740697
CONTROL PANEL(S) 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 144 100 4.4
standby / prime+10% 110% 50.0 400 312 220 88 96 3.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.1 DENSITY 100.1
TEMPERATURE (Deg c) 3 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 72 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 13.03.2014