Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10711 CE: YES
RATED OUTPUT KVA 250 RATING CLASSIFICATION PRP
KW 200
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 348 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGHF7004
ENGINE MODEL 1306C-E87TAG6 SERIAL NUMBER N12599V
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO381LN/4 SERIAL NUMBER 0001536715
CONTROL PANEL(S) 7210 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 36%% 50.0 415 100 72 4.4
standby / prime+10% 110% 50.0 415 306 220 88 93 2.9
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 11 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 93 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 08.11.2011