Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10517/A CE:
RATED OUTPUT KVA 250 RATING CLASSIFICATION PRP
KW 200
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 361 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGHF7004
ENGINE MODEL 1306CE87TAG6 SERIAL NUMBER N11136V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCD274K SERIAL NUMBER 0269566/017
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 136 94 4.2
standby / prime+10% 110% 50.0 400 318 220 90 97 3.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.9 DENSITY 101.9
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 62 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 24.05.2011