Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11456/B CE: NO
RATED OUTPUT KVA 235/258 RATING CLASSIFICATION PRP/ESP
KW 188/206
PHASE 3
VOLTS 220/127 PERFORMANCE CLASS G1
AMPS 617/677 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGDF7197
ENGINE MODEL 1306C-E87TAG3 SERIAL NUMBER N11826X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 38-3SN/4 SERIAL NUMBER 1684288
CONTROL PANEL(S) DSE 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.0 220 247 94 20 - 4.8
standby / prime+10% 110% 60.0 220 543 207 88 - 3.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 15 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 76 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 02.10.2013