Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11049/C CE: NO
RATED OUTPUT KVA 235 RATING CLASSIFICATION PRP/ESP
KW 188
PHASE 3
VOLTS 220/127 PERFORMANCE CLASS G1
AMPS 678 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGDF7008
ENGINE MODEL E87TAG3 SERIAL NUMBER N11603W
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO383SN SERIAL NUMBER 1623446
CONTROL PANEL(S) DSE 7220 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.0 220 246 94 5.8
standby / prime+10% 110% 60.0 220 542 206 88 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 99.8 DENSITY 99.8
TEMPERATURE (Deg c) 15 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 62 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 02.10.2012