Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11283/B CE: NO
RATED OUTPUT KVA 230 RATING CLASSIFICATION PRP
KW 184
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 350 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGDF7005
ENGINE MODEL 1306-E87TAG3 SERIAL NUMBER N10544X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO38-3SN SERIAL NUMBER 1672458
CONTROL PANEL(S) 7320 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 65% 60.0 380 182 120 4.4
standby / prime+10% 110% 60.0 380 308 202 88 99 3.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.8 DENSITY 101.8
TEMPERATURE (Deg c) 11 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 60 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 30.04.2013