Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E11124/A | CE: | NO | |||||
| RATED OUTPUT | KVA | 200 | RATING CLASSIFICATION | PRP | ||||
| KW | 160 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 380/220 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 304 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | E.C.M. | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | WGDF7002 | |||||
| ENGINE MODEL | 1306-E87TAG3 | SERIAL NUMBER | N11869W | |||||
| ALTERNATOR MAKE | STAMFORD | |||||||
| ALTERNATOR MODEL | UCI274H | SERIAL NUMBER | A12H328057 | |||||
| CONTROL PANEL(S) | 7120 | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 50.0 | 380 | 109 | 72 | 4.3 | ||
| standby / prime+10% | 110% | 50.0 | 380 | 268 | 176 | 87 | 3.3 | |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 101.2 | DENSITY | 101.2 | |||||
| TEMPERATURE (Deg c) | 9 | CALORIFIC VALUE | 42.5 MJ/kg | |||||
| HUMIDITY (%) | 76 | LUB OIL SPEC | Multigrade | |||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | ijohnson | DATE | 22.04.2016 20.10.2012 | |||||