Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10707/A CE: NO
RATED OUTPUT KVA 200 RATING CLASSIFICATION PRP
KW 160
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 278 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER WGDF7002
ENGINE MODEL 1306C-E87TAG3 SERIAL NUMBER N12238V
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO38-2SN/4 SERIAL NUMBER A1094063
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 128 91 4.6
standby / prime+10% 110% 50.0 415 245 176 88 94 3.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.0 DENSITY 101.0
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 88 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 31.10.2011