Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10333 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ECM COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER WGDF7002
ENGINE MODEL 1306C-E87TAG3 SERIAL NUMBER N11680U
ALTERNATOR MAKE MECC ALTE
ALTERNATOR MODEL ECO 38-2SN/4 SERIAL NUMBER A1098725
CONTROL PANEL(S) DSE7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 104 72 25 - 4.3
standby / prime+10% 110% 50 400 254 176 88 - 3.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.5 DENSITY 101.5
TEMPERATURE (Deg c) 6 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 100 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 22.02.2011