Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11684 CE: NO
RATED OUTPUT KVA 440 RATING CLASSIFICATION PRP
KW 352
PHASE 3
VOLTS 480/277 PERFORMANCE CLASS G1
AMPS 529 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER TGHF5126
ENGINE MODEL 2206A-E13TAG6 SERIAL NUMBER U18454W
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444F SERIAL NUMBER A14B077594
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 60.0 480 254 211 4.8
standby / prime+10% 110% 60.0 480 466 387 88 3.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.6 DENSITY 100.6
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 76 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 02.04.2014