Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10857/D CE: NO
RATED OUTPUT KVA 360 RATING CLASSIFICATION PRP
KW 288
PHASE 3
VOLTS 220/127 PERFORMANCE CLASS G1
AMPS 945 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER TGBF5112
ENGINE MODEL 2206A-E13TAG2 SERIAL NUMBER U24534V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444E SERIAL NUMBER 0276568/014
CONTROL PANEL(S) DSE 7320 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.0 220 378 144 - - 4.9
standby / prime+10% 110% 60.0 220 831 317 88 - 3.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 104.2 DENSITY 104.2
TEMPERATURE (Deg c) 1 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 80 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 08.02.2012