Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10627 CE: NO
RATED OUTPUT KVA 300 RATING CLASSIFICATION PRP
KW 240
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 433 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECM COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER TGBF5112
ENGINE MODEL 2206AE13TAG2 SERIAL NUMBER U19554V
ALTERNATOR MAKE MECCALTE
ALTERNATOR MODEL ECO382LN4 SERIAL NUMBER 0001522636
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 50.0 400 208 144 4.6
standby / prime+10% 110% 50.0 400 381 264 88 2.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.5 DENSITY 101.5
TEMPERATURE (Deg c) 17 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 59 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 31.08.2011