Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10214 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ECM COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER TGBF5112
ENGINE MODEL 2206AE13TAG2 SERIAL NUMBER U19005U
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444E SERIAL NUMBER 0269579/027
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 380 255 168 4.5
standby / prime+10% 110% 50 380 468 308 84 2.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.2 DENSITY 102.2
TEMPERATURE (Deg c) 4 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 08.02.2011