Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10157 CE:
RATED OUTPUT KVA RATING CLASSIFICATION G1
KW
PHASE
VOLTS PERFORMANCE CLASS PRP
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ELECTRONIC COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER RS51302
ENGINE MODEL 1104A-44TG1 SERIAL NUMBER U525139V
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO323L4 SERIAL NUMBER 1462625
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 380 78 51 5.1
standby / prime+10% 110% 50 380 95 63 84 4.5
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102 DENSITY 102
TEMPERATURE (Deg c) 5 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 81 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 03.02.2011