Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11409/E CE: NO
RATED OUTPUT KVA 80 RATING CLASSIFICATION PRP
KW 64
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 115 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51277
ENGINE MODEL 1104A-44TG2 SERIAL NUMBER U576518X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP34-1S SERIAL NUMBER 0001687810
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 83 52 - - 5.06
standby / prime+10% 110% 50 400 101 70 83 - 3.44
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.3 DENSITY 102.3
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 77 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 25.07.2013