Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11365/E CE: NO
RATED OUTPUT KVA 80 RATING CLASSIFICATION PRP
KW 64
PHASE 3
VOLTS 415 PERFORMANCE CLASS G1
AMPS 111 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51277
ENGINE MODEL 1104A-44TG2 SERIAL NUMBER U575976X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP34-1S SERIAL NUMBER 1675824
CONTROL PANEL(S) DSE7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 415 89 51 - - 5.06
standby / prime+10% 110% 50 415 122 70 82 - 3.89
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 82 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 98 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 28.06.2013