Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10616 CE: NO
RATED OUTPUT KVA 75 RATING CLASSIFICATION PRP
KW 60
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 114 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51277
ENGINE MODEL 1104A-44TG2 SERIAL NUMBER U528343V
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI224F SERIAL NUMBER 0269491/022
CONTROL PANEL(S) SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.6 380 73 48 6.0
standby / prime+10% 110% 60.0 380 100 66 78 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.9 DENSITY 100.9
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 73 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 02.09.2011