Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12890/D CE: NO
RATED OUTPUT KVA 65 RATING CLASSIFICATION PRP
KW 52
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 94 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51276
ENGINE MODEL 1104A-44TG1 SERIAL NUMBER U615006A
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP32-3L/4 SERIAL NUMBER 0001901541
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 400 56 39 5.7
standby / prime+10% 110% 50.0 400 83 57 84 4.0
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.9 DENSITY 101.9
TEMPERATURE (Deg c) 14 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 78 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 13.07.2017