Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12111 CE: YES
RATED OUTPUT KVA 65 RATING CLASSIFICATION PRP
KW 52
PHASE 3
VOLTS 415/230 PERFORMANCE CLASS G1
AMPS 90 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RS51276
ENGINE MODEL 1104A-44TG1 SERIAL NUMBER U596827Y
ALTERNATOR MAKE MECCALTE
ALTERNATOR MODEL ECO32-3L/4 SERIAL NUMBER 0001841032
CONTROL PANEL(S) SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 100% 50 415/230 72 52 5.41
standby / prime+10% 110% 50 415/230 80 57 82 3.93
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.4 DENSITY 102.4
TEMPERATURE (Deg c) 15 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 51 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY kevin DATE 22.04.2016 15.06.2015