Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10829 CE: NO
RATED OUTPUT KVA 100 RATING CLASSIFICATION PRP
KW 80
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 144 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RJ51437
ENGINE MODEL 1104C-44TAG2 SERIAL NUMBER U547183V
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP34-2S/4 SERIAL NUMBER 0001557729
CONTROL PANEL(S) DSE7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 75% 50.0 400 86 60 82 5.5
standby / prime+10% 110% 50.0 400 126 88 4.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 103.8 DENSITY 103.8
TEMPERATURE (Deg c) 3 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 69 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY grustill DATE 22.04.2016 01.02.2012