Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13108/E CE: NO
RATED OUTPUT KVA 124 RATING CLASSIFICATION ESP
KW 99
PHASE 3
VOLTS 220/127 PERFORMANCE CLASS G1
AMPS 325 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE ELECTRONIC COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER RJ51175
ENGINE MODEL 1104C-44TAG2 SERIAL NUMBER U650655C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI274D SERIAL NUMBER C17D172283
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60 220 130 50 6.0
standby / prime+10% 110% 60 220 260 99 84 4.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.4 DENSITY 101.4
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 71 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 17.04.2018