Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10336 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE ELECTRONIC COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER RJ51175
ENGINE MODEL 1104C-44TAG2 SERIAL NUMBER U524604U
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI274C SERIAL NUMBER 0269516/014
CONTROL PANEL(S) DSE7310 SERIAL NUMBER(S) 3195064
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 84 60 37 - 5.5
standby / prime+10% 110% 50.0 415 123 88 83 - 4.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.4 DENSITY 100.4
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 81 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S) 10-177000
TESTED BY hwalsh DATE 22.04.2016 12.03.2011