Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12182/G CE: NO
RATED OUTPUT KVA 160 RATING CLASSIFICATION PRP
KW 128
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 243 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER PR82217
ENGINE MODEL 1106A-70TAG2 SERIAL NUMBER U050699A
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL UCI274E SERIAL NUMBER A15H333272
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 75% 60.5 380 146 96 6.1
standby / prime+10% 110% 60.0 380 214 141 83 4.7
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 12 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 74 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 04.09.2015