Generating Set Functional Test Report |
||||||||
In accordance with ISO 8528 - 6 2005 |
||||||||
| PLANT NUMBER: | E12505/E | CE: | NO | |||||
| RATED OUTPUT | KVA | 150 | RATING CLASSIFICATION | PRP | ||||
| KW | 120 | |||||||
| PHASE | 3 | |||||||
| VOLTS | 400/230 | PERFORMANCE CLASS | G1 | |||||
| AMPS | 217 | (AS DEFINED BY ISO 8528-1) | ||||||
| HZ | 50.0 | |||||||
| RPM | 1500 | |||||||
| GOVERNOR TYPE | MECHANICAL | COOLING METHOD | LIQUID | |||||
| ENGINE MAKE | PERKINS | BUILD NUMBER | PR82148 | |||||
| ENGINE MODEL | 1106A-70TAG2 | SERIAL NUMBER | U048582Y | |||||
| ALTERNATOR MAKE | MECC-ALTE | |||||||
| ALTERNATOR MODEL | ECP34-2L/4 | SERIAL NUMBER | 0001947387 | |||||
| CONTROL PANEL(S) | 7120 MKII | SERIAL NUMBER(S) | ||||||
| SWITCHGEAR | SERIAL NUMBER(S) | |||||||
| LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
| LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
| type | % | TEMP | TEMP | PRESS | ||||
| DEG C | DEG C | BAR | ||||||
| load acceptance | % | 50.7 | 400 | 104 | 72 | 5.7 | ||
| standby / prime+10% | 110% | 50.0 | 400 | 191 | 132 | 79 | 4.2 | |
|
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
| 85 | ||||||||
| AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
| ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
| BAROMETRIC PRESSURE (kpa) | 98.9 | DENSITY | ||||||
| TEMPERATURE (Deg c) | CALORIFIC VALUE | 42.5 MJ/kg | ||||||
| HUMIDITY (%) | LUB OIL SPEC | Multigrade | ||||||
| WIRING DIAGRAMS: | ||||||||
| ENGINE | CONTROL PANEL(S) | |||||||
| TESTED BY | ijohnson | DATE | 22.04.2016 28.09.2016 | |||||