Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12433 CE: NO
RATED OUTPUT KVA 500 RATING CLASSIFICATION PRP
KW 400
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 696 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER MGBF5138
ENGINE MODEL 2506A-E15TAG2 SERIAL NUMBER N02528A
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 40-1L/4 SERIAL NUMBER 0001923742
CONTROL PANEL(S) DSE 7310 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 279 200 24 6.4
standby / prime+10% 110% 50.0 415 613 440 88 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.4 DENSITY 101.4
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 64 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 27.05.2016