Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E9703 CE:
RATED OUTPUT KVA RATING CLASSIFICATION PRP
KW
PHASE
VOLTS PERFORMANCE CLASS G1
AMPS (AS DEFINED BY ISO 8528-1)
HZ
RPM
GOVERNOR TYPE E.C.U. COOLING METHOD
ENGINE MAKE PERKINS BUILD NUMBER MGBF5120
ENGINE MODEL 2506AE15TAG2 SERIAL NUMBER U10756U
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544D SERIAL NUMBER 0261412/011
CONTROL PANEL(S) 7120 SERIAL NUMBER(S) 3021034
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 415 334 240 5.3
standby / prime+10% 110% 50 415 612 440 88 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.5 DENSITY 100.5
TEMPERATURE (Deg c) 14 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 94 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 04.08.2010