Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12459 CE: NO
RATED OUTPUT KVA 500 RATING CLASSIFICATION PRP
KW 400
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 760 (AS DEFINED BY ISO 8528-1)
HZ 60
RPM 1800
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER MGAF5137
ENGINE MODEL 2506A-E15TAG1 SERIAL NUMBER N02466A
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544D SERIAL NUMBER A16E218830
CONTROL PANEL(S) DSE 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 60.0 380 304 200 20 5.8
standby / prime+10% 110% 60.0 380 669 440 88 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.3 DENSITY 102.3
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 88 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 28.06.2016