Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11578/D CE: NO
RATED OUTPUT KVA 510 RATING CLASSIFICATION PRP
KW 408
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 775 (AS DEFINED BY ISO 8528-1)
HZ 60.0
RPM 1800
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER MGAF5125
ENGINE MODEL 2506A-TAG1 SERIAL NUMBER U18078X
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544D SERIAL NUMBER A13K469501
CONTROL PANEL(S) 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 60% 60.0 381 372 245 5.2
standby / prime+10% 110% 60.0 380 682 449 88 4.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.1 DENSITY 100.1
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 79 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 03.01.2014