Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12565 CE: NO
RATED OUTPUT KVA 300 RATING CLASSIFICATION PRP
KW 240
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 434 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER LGFF1010
ENGINE MODEL 1506A-E88TAG5 SERIAL NUMBER N00512A
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI444D SERIAL NUMBER A14D175552
CONTROL PANEL(S) DSE 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 173 120 18 5.6
standby / prime+10% 110% 50.0 400 382 264 88 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.4 DENSITY 102.4
TEMPERATURE (Deg c) 10 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 92 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 11.10.2016