Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12649/B CE: YES
RATED OUTPUT KVA 225 RATING CLASSIFICATION PRP
KW 180
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 313 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER LGBF1014
ENGINE MODEL 1506A-E88TAG2 SERIAL NUMBER N00919A
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO 38-3S4 SERIAL NUMBER 0001895709
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 415 125 90 10 5.9
standby / prime+10% 110% 50.0 415 276 198 86 4.4
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.1 DENSITY 101.1
TEMPERATURE (Deg c) 5 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 80 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 29.11.2016