Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11381 CE: NO
RATED OUTPUT KVA 650 RATING CLASSIFICATION PRP
KW 520
PHASE 3
VOLTS 380/220 PERFORMANCE CLASS G1
AMPS 988 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER JGBF5119
ENGINE MODEL 2806A-E18TAG2 SERIAL NUMBER U13091X
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544F SERIAL NUMBER A13D160541
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 380 790 520 24 - 5.3
standby / prime+10% 110% 50.0 380 869 572 89 - 4.2
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.6 DENSITY 101.6
TEMPERATURE (Deg c) 18 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 11.07.2013