Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13140 CE: NO
RATED OUTPUT KVA 600 RATING CLASSIFICATION PRP
KW 480
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 867 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER JGAF5257
ENGINE MODEL 2806A-E18TAG1A SERIAL NUMBER N03637C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544E SERIAL NUMBER A17K465767
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.0 400 347 240 10 5.5
standby / prime+10% 110% 50.0 400 763 528 88 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.2 DENSITY 100.2
TEMPERATURE (Deg c) 8 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 89 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 27.03.2018