Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11817/A CE: NO
RATED OUTPUT KVA 600 RATING CLASSIFICATION PRP
KW 480
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 835 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE E.C.M. COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER JGAF5099
ENGINE MODEL 2806A-E18TAG1A SERIAL NUMBER U16629Y
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECO40-1.5L/4 SERIAL NUMBER 0001785611
CONTROL PANEL(S) 7310 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 80% 50.0 416 534 384 5.2
standby / prime+10% 110% 50.0 415 735 528 89 81 3.6
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.9 DENSITY 100.9
TEMPERATURE (Deg c) 20 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 82 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 03.09.2014