Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E10987 CE: NO
RATED OUTPUT KVA 600 RATING CLASSIFICATION PRP
KW 480
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 867 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE ECU COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER JGAF5004
ENGINE MODEL 2806A-E18TAG1A SERIAL NUMBER U15624W
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL HCI544E SERIAL NUMBER 0284518/002
CONTROL PANEL(S) DSE 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 694 480 - - 5.3
standby / prime+10% 110% 50 400 763 528 89 - 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 16 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 87 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 10.07.2012