Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12367/B CE: NO
RATED OUTPUT KVA 20 RATING CLASSIFICATION PRP
KW 16
PHASE 3
VOLTS 415/240 PERFORMANCE CLASS G1
AMPS 28 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GV51790
ENGINE MODEL 404A-22G1 SERIAL NUMBER U964642B
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-M4 SERIAL NUMBER 0001908257
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.5 415 18 13 4.8
standby / prime+10% 110% 50.0 415 25 17.6 82 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.1 DENSITY 101.1
TEMPERATURE (Deg c) 7 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 80 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 13.04.2016