Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E12311 CE: NO
RATED OUTPUT KVA 15 RATING CLASSIFICATION PRP
KW 15
PHASE 1
VOLTS 220 PERFORMANCE CLASS G1
AMPS 68 (AS DEFINED BY ISO 8528-1)
HZ 50.0
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GV51790
ENGINE MODEL 404A-22G1 SERIAL NUMBER U959840B
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-VL/4 SERIAL NUMBER 0001899976
CONTROL PANEL(S) 7120 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.4 220 54 12 5.0
standby / prime+10% 110% 50.0 220 75 16.5 80 3.8
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.2 DENSITY 101.2
TEMPERATURE (Deg c) 6 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 79 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY ijohnson DATE 22.04.2016 29.02.2016