Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11072/A CE: NO
RATED OUTPUT KVA 20 RATING CLASSIFICATION PRP
KW 16
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 29 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD WATER
ENGINE MAKE PERKINS BUILD NUMBER GV51790
ENGINE MODEL 404D-22G SERIAL NUMBER K967998W
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-1LN/4 SERIAL NUMBER 00015516188
CONTROL PANEL(S) DSE 7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 52 400 18 13 5.4
standby / prime+10% 110% 50 400 25 17 85 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100 DENSITY 100
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 79 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 05.09.2012