Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11226/A CE: NO
RATED OUTPUT KVA 13 RATING CLASSIFICATION PRP
KW 10
PHASE 3
VOLTS 400 PERFORMANCE CLASS G1
AMPS 19 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GU51794
ENGINE MODEL 403A-15G1 SERIAL NUMBER U539924W
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP3-2LN4 SERIAL NUMBER 0001595968
CONTROL PANEL(S) DSE7120 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50 400 23 12 50 - 5.43
standby / prime+10% 110% 50 400 30 17 80 - 4.32
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
85
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 98 DENSITY 98
TEMPERATURE (Deg c) 0 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 78 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY michael DATE 22.04.2016 13.02.2013