Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13250/A CE: NO
RATED OUTPUT KVA 18 RATING CLASSIFICATION PRP
KW 14.4
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 26 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GN66044
ENGINE MODEL 404D-22G SERIAL NUMBER U931839D
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL S1L2-J SERIAL NUMBER B18J408380
CONTROL PANEL(S) DSE 7320 MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 100% 51.1 400 21 14 4.7
standby / prime+10% 110% 50.0 400 23 16 80 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 101.4 DENSITY 101.4
TEMPERATURE (Deg c) 19 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 55 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 09.10.2018