Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E13036 CE: YES
RATED OUTPUT KVA 18 RATING CLASSIFICATION PRP
KW 14.4
PHASE 1
VOLTS 240 PERFORMANCE CLASS G1
AMPS 75 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD LIQUID
ENGINE MAKE PERKINS BUILD NUMBER GN66044
ENGINE MODEL 404D-22G SERIAL NUMBER U908750C
ALTERNATOR MAKE STAMFORD
ALTERNATOR MODEL PI144G SERIAL NUMBER B16L492282
CONTROL PANEL(S) DSE 7120MKII SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance % 50.9 240 60 14 37 4.7
standby / prime+10% 110% 50.0 400 66 16 78 4.1
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 100.8 DENSITY 100.8
TEMPERATURE (Deg c) 14 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 78 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 21.11.2017