Generating Set Functional Test Report

In accordance with ISO 8528 - 6 2005

PLANT NUMBER: E11557/A CE:
RATED OUTPUT KVA 20 RATING CLASSIFICATION PRP
KW 13
PHASE 3
VOLTS 400/230 PERFORMANCE CLASS G1
AMPS 18 (AS DEFINED BY ISO 8528-1)
HZ 50
RPM 1500
GOVERNOR TYPE MECHANICAL COOLING METHOD L
ENGINE MAKE PERKINS BUILD NUMBER GN65732
ENGINE MODEL 404D-22G SERIAL NUMBER U902862X
ALTERNATOR MAKE MECC-ALTE
ALTERNATOR MODEL ECP28-M/4 SERIAL NUMBER 0001723766
CONTROL PANEL(S) DSE 7110 SERIAL NUMBER(S)
SWITCHGEAR SERIAL NUMBER(S)
LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type % TEMP TEMP PRESS
DEG C DEG C BAR
load acceptance 110% 50.0 400 18 13 5.1
standby / prime+10% 110% 50.0 400 25 17 84 4.3
GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)
IP
75
AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M) Sea Level FUEL SPEC BS2869A2
BAROMETRIC PRESSURE (kpa) 98.9 102.4 DENSITY 102.4
TEMPERATURE (Deg c) 4 CALORIFIC VALUE 42.5 MJ/kg
HUMIDITY (%) 88 LUB OIL SPEC Multigrade
WIRING DIAGRAMS:
ENGINE CONTROL PANEL(S)
TESTED BY hwalsh DATE 22.04.2016 20.02.2014